product description: |
KST Round &Standard Cooling Towers
Characteristics:
1. From 3RT to 1500RT, complete models are suitable for all different requirements. 2. Having F.R.P and heating zincification iron as mayor structure materials, they are characterized by lightness, stability and anticorrosion. 3. It is easy to install and suitable for all spots. 4. Round-shape design and air resistance to keep out strong wind, which is most suitable for frequent typhoon areas. |
MODEL |
Dimension |
Fan Motor |
Fan Dia |
Air Volumn |
Pump Head |
WEIGHT |
KST
KST-M
KST-HC |
m/m |
HP(KW) |
DФ
m/m |
m3/min |
M |
Kgs |
H |
D |
Dry |
Operating |
3 |
1183 |
750 |
1/6(0.12) |
500 |
45 |
0.9 |
28 |
60 |
5 |
1333 |
750 |
1/6(0.12) |
500 |
55 |
1.2 |
32 |
68 |
8 |
1518 |
860 |
1/6(0.12) |
500 |
70 |
1.3 |
43 |
78 |
10 |
1643 |
860 |
1/4(0.18) |
500 |
100 |
1.3 |
79 |
150 |
15 |
1563 |
1165 |
1/4(0.18) |
600 |
140 |
1.5 |
109 |
285 |
20 |
1763 |
1165 |
1/2(0.37) |
600 |
180 |
1.7 |
129 |
318 |
25 |
1790 |
1165 |
1(0.75) |
600 |
150 |
1.9 |
137 |
334 |
30 |
1705 |
1560 |
1(0.75) |
700 |
195 |
1.9 |
144 |
522 |
40 |
1825 |
1560 |
1(0.75) |
700 |
210 |
2 |
185 |
577 |
50 |
2080 |
1560 |
2(1.5) |
900 |
280 |
2.1 |
228 |
632 |
60 |
1770 |
1900 |
2(1.5) |
900 |
370 |
2.1 |
277 |
719 |
70 |
2180 |
1900 |
2(1.5) |
1200 |
390 |
2.3 |
337 |
798 |
80 |
1920 |
2140 |
2(1.5) |
1200 |
450 |
2.5 |
352 |
982 |
100 |
2860 |
2410 |
3(2.2) |
1500 |
500 |
2.8 |
474 |
1205 |
125 |
2130 |
2730 |
3(2.2) |
1500 |
700 |
3 |
524 |
1336 |
150 |
2400 |
2730 |
5(3.7) |
1800 |
840 |
3.2 |
702 |
1583 |
175 |
2350 |
3280 |
5(3.7) |
1800 |
1100 |
3.2 |
855 |
3415 |
200 |
2450 |
3280 |
5(3.7) |
1800 |
1100 |
3.3 |
937 |
3570 |
225 |
3000 |
3280 |
7 1/2(5.5) |
2400 |
1300 |
3.4 |
1022 |
3661 |
250 |
2790 |
3760 |
7 1/2(5.5) |
2400 |
1580 |
3.6 |
1172 |
3885 |
300 |
3130 |
3760 |
10(7.5) |
2400 |
1820 |
3.8 |
1331 |
4125 |
350 |
3360 |
4600 |
10(7.5) |
2400 |
2120 |
4 |
1560 |
5690 |
400 |
3970 |
4600 |
15(11) |
3000 |
2260 |
4.2 |
1902 |
6145 |
500 |
4050 |
4870 |
15(11) |
3000 |
3250 |
4.5 |
2165 |
6537 |
600 |
3940 |
5580 |
20(15) |
3400 |
3500 |
4.5 |
2909 |
8052 |
700 |
4150 |
6550 |
20(15) |
3400 |
4250 |
5 |
3411 |
11734 |
800 |
4150 |
6550 |
30(22) |
3400 |
4500 |
5.5 |
3963 |
12690 |
1000 |
4940 |
6550 |
30(22) |
3600 |
4830 |
5.8 |
4512 |
13465 |
1250 |
5090 |
7600 |
40(30) |
4200 |
6700 |
6.3 |
4650 |
14500 |
1500 |
5670 |
8430 |
50(37.5) |
4200 |
7900 |
7 |
5500 |
21500 |
Note:
1. Standard design conditions: hot water of 37℃, cold water of 32℃, ambient wet bulb of 28℃ 2. Quality of heat counting Kcal/hr is: Q=MST Quality of flow (LPM)*1*△T*60= Kcal/hr
Quality of Heat:Kcal/hr:Q=MST Current Measure:(l/min)*1*ΔT*60=____Kcal/h
|